Inicio >Productos >banco de carga
Resistive 100kw Load Bank For Generator resting
Testing capacity:0 - 400 kw
Type of load:Resistive or Reactive, PF = 1.0 or 0.8
Duty:Continuous
Cooling system:Industrial grade axial fan
Phase:Available at both single and thr
  • Detail
  • Order

99c1463e-7a10-4e91-ad70-895e15a4ede6.jpg

KEYPOWER Load Bank Technical Specifications  
1. Resistive type of load, PF = 1.0. Stainless steel sheathed elements manufactured from high grade nickel-chromium alloys resistive wire covered by 3-year warranty.     
2. Rated testing voltage: AC 3P4W, 110-480 VAC 50/60HZ.     
3. Cooling mode: forced air-cooled, fans mounted on the side of the load bank blow horizontally. External utility power or internal tested power supply for fans.     
4. Working mode: load step control
Total testing capacity ranges from 0kw to the max consisting of 10kw, 20kw, 50kw, 100kw load setting switches plus a 0-10kw fine-tuning knob. From 0kw to the max, any load combination is achievable. Load step resolution is 10kw.  
5. Load bank features world-famous components to ensure reliable performance and longer service life including:

  contactors.
  switches, knobs and indicators.
  circuit breakers.
  intermediate relays.
  terminal blocks.

6. Parameter measuring accuracy grade: 0.5.
7. Load control accuracy: ±3%.
8. Load bank protections: over heating protection, cooling fans failure protection and over load protection with alarm.
9. Control mode: two control modes available: a) Local manual control; b) Optional: Manual control via a remote control panel (max control distance is 20m).
10. Parameter display and measurement: Control panel contains a    Multifunction Electricity Meter displaying voltage, current, load power, reactive power, apparent power, power factor, frequency etc. (Optional: a professional generator tester displays and measures all sorts of steady, dynamic parameters as well as harmonic wave, can be connected to a PC for data recording and test report printing).

11. Operating environment: Altitude: ≤1000m above sea level. Ambient temp: -10℃~+40℃ Relative humidity: ≤80% ventilated environment without explosive or corrosive dust. Not allowed to use in rainy outdoor environment.

1512435608134293.jpg

grupo electrógeno diesel - GFF keypower fabricante del grupo electrógeno
Tel: 86-591-83405668 | Skype ID: lily-wang2005
Url:www.gff-keypower.com | www.loadbank.cc
Email:Lily@keypower.biz | sales@keypower.biz

Seguienos

Copyright © 2018 grupo electrógeno diesel - GFF keypower fabricante del grupo electrógeno All Rights Reserved. 闽ICP备: 14010591号-1