Home > >Notes for installation of...
Notes for installation of generator sets

1, diesel generator installation site should be well ventilated, the generator end should have enough air inlet, diesel engine end should have a good air outlet.The air outlet area should be more than 1.5 times the area of the water tank.

2, the generator installation should be kept clean around, avoid placing in the vicinity can produce acid, alkaline and other corrosive gases and steam items.Conditional should be equipped with fire extinguishing devices.

3. For indoor use, the smoke exhaust pipe must be channeled outdoors. The pipe diameter must be greater than the diameter of the smoke outlet pipe of the muffler, and the elbow of the pipe connected should not be more than 3 to ensure the smooth smoke exhaust.If the exhaust pipe is installed vertically, a rain shield must be installed.

4. When the foundation is concrete, the levelness shall be measured with a level ruler during installation to make the unit fixed on the horizontal basis.There should be special shockproof pad or bottom bolt between the unit and the foundation.

5. The unit shell must have reliable protective grounding. For generators requiring direct grounding of the neutral point, neutral grounding must be carried out by professionals, and lightning protection device is configured.

6. The two-way switch between the diesel generator and the mains power must be very reliable in order to prevent back power supply.The wiring reliability of the two-way switch shall be inspected and approved by the local power supply department.


KEYPOWER | Generator and Load Bank Manufacturer
Tel: 86-591-83405668 | Skype ID: lily-wang2005
Url:www.gff-keypower.com | www.loadbank.cc
Email:Lily@keypower.biz | sales@keypower.biz

Follow me

Copyright © 2018 KEYPOWER | Generator and Load Bank Manufacturer All Rights Reserved. 闽ICP备: 14010591号-1